With its integrated pressure measurement cell, 4-digit display and 4 switching outputs, the EDS 1700 offers the user all the advantages of a modern electronic pressure switch. 4 switching points and switch-back points can be adjusted very simply and independently of one another using the keypad.

For optimum integration in monitoring systems (e.g. with PLC), an Analog output (4 to 20 mA or 0 to 10 V) is also available.

The main areas of application of the EDS 1700 are in hydraulics and pneumatics.more
Unit of Measure

Specifications

Type

Electronic Pressure Switch

Model Code Description

EDS 1791-N-400-000

Signal (Selectable)

4 to 20 mA0 to 10 V

Direct Current (DC) Supply Voltage

22 to 32 V

Approximate Current Consumption

200 mA

Residual Ripple of Supply Voltage

≤ 10 %

Display

4-Digit, LED, 7 Segment, Red, Height of Digits 13 mm

Electrical Connection

14-Pole, Terminal Block

Housing Material

Anodized Aluminum

Weight

~800 g

Switching Function

Adjustable N/O or N/C

Power Supply

22 to 32 VDC

Accuracy

1 %

BUn

EA

Recommended Tightening Torque

20 N·m

Division

ELECTRONICS

Product Group Family

PRESSURE SWITCHES

Product

PRESSURE SWITCHES

Input Data

Input Measuring Pressure Range

400 bar5800 psi

Input Overload Pressure

800 bar11600 psi

Burst Pressure

2000 bar29000 psi

Input Mechanical Connection Type

Threaded port G/14 DIN 3852

Input Mechanical Connection Size

G1/4

Input Mechanical Connection

Threaded Port

Torque Value

20 N·m15 lb·ft

Material of Connection

Stainless Steel

Output Data

Output Accuracy at Minimum Setting Best Fit Straight Line (B.F.S.L) for EDS 1700-P (Full Scale)

≤ ± 0.25 %

Output Accuracy at Minimum Setting Best Fit Straight Line (B.F.S.L) for EDS 1700-N (Full Scale)

≤ ± 0.5 %

Maximum Repeatability for EDS 1700-P

≤ ± 0.25 %

Maximum Repeatability for EDS 1700-N

≤ ± 0.5 %

Temperature Drift for EDS 1700-P at Maximum Zero Point and Range (Full Scale)

≤ ± 0.012 ºF

Temperature Drift for EDS 1700-N at Maximum Zero Point and Range (Full Scale)

≤ ± 0.017 ºF

Switch Outputs

Switch Output Type

4 Relays w/changeover contacts (2 groups, common supply of each group connected)

Alternate Current (AC)/Direct Current (DC) Switching Voltage

0.1 to 250 V

Maximum Switching Capacity

50 W400 V·A

Maximum Switching Current Per Switch Output

0.01 to 2 A

Switching Cycles at Minimum Load In Million

20

Switching Cycles at Maximum Load In Million

1

Approximate Reaction Time

20 ms

Environmental Conditions

Compensated Temperature Range

14 to 158 ºF

Operating Temperature Range

-13 to 158 ºF

Storage Temperature Range

-13 to 176 ºF

Fluid Temperature Range

-13 to 176 ºF

CE Mark

EN 61000-6-1/2/3/4

Vibration Resistance According to DIN EN 60068-2-6 at 0 to 500 Hz

≤ 5 g

Shock Resistance According to DIN EN 60068-2-6 at 10 to 500 Hz Per 1 ms

≤ 10 g

Protection Class According to DIN IEC 60529

IP 65

Terminal Assignment

Pin Connection 1

+UB

Pin Connection 2

0 Voltage

Pin Connection 3

Analog Output Signal +

Pin Connection 4

Analog Output Signal - (0 Voltage)

Pin Connection 5

Relay 1 N/C

Pin Connection 6

Relay 1 N/O

Pin Connection 7

Center Relay 1 and 2

Pin Connection 8

Relay 2 N/C

Pin Connection 9

Relay 2 N/O

Pin Connection 10

Relay 3 N/C

Pin Connection 11

Relay 3 N/O

Pin Connection 12

Center Relay 3 and 4

Pin Connection 13

Relay 4 N/C

Pin Connection 14

Relay 4 N/O

Special Features

N/A

  • Integrated pressure sensor with strain gauge on stainless steel membrane
  • Simple operation via key programming
  • 4 limit relays, switching points and switch back points can be adjusted independently
  • Analog output signal selectable
  • Many useful additional functions
  • Optional mounting position (pressure connection on the top/ bottom, keypad and display can be turned through 180°)
  • Can be set to display values in any unit of measurement e.g.: kN, kg, psi

Setting Options

N/A The core of the unit is a microprocessor which provides many useful extra functions in addition to normal pressure switch operation. It is possible, for example, to activate switching delay times to prevent fast pressure peaks from triggering an unwanted switching cycle. All settings are made using the keypad.

Setting Ranges of the Switching Points

N/A

  • Switching point relay 1 to 4: 1.5 % to 100 % FS
  • Switch-back relay 1 to 4: 1 % to 99 % FS or alternatively switch-back hysteresis 1 to 4: 1 % to 99 % FS

Note for Setting Ranges of the Switching Points

FS (Full Scale) = Relative to the Full Measurement Range

Additional Setting Options

N/A

  • Switching direction of the relays 1 to 4 (N/C or N/O)
  • Switch-on delay relays 1 to 4 in the range 0.00 .. 90 seconds
  • Switch-off delay relays 1 to 4 in the range 0.00 to 90 seconds
  • Switch-back mode (either switch-back point or switch-back hysteresis)
  • Display of the actual pressure, a switching point or of the peak value
  • Display filter (slow/medium/fast)
  • Display range scale individually adaptable (bar, psi, user-selectable)
  • Measurement unit (bar, psi) is displayed
  • Analog output (4 to 20 mA or 0 to 10 V)
  • Programming disable

Accessories

N/A Appropriate accessories, such as mechanical adapters etc. can be found in the accessories brochure.

Note

N/A Reverse polarity protection of the supply voltage, excess voltage, override and short circuit protection are provided.